That matters wherever the cooled equipment is sensitive to scale, fouling or corrosion - induction heating coils, welders, laser sources, injection mould tooling, engine test cells. A tower loop picks up dust, oxygen and biological growth and loses water to evaporation; a closed loop does not, and with glycol it can run outdoors through the winter.
Four figures and the site.
| RANGE | TYPE | COVERS | RATING | PART NUMBERS |
| Packaged Coolers | Closed-Circuit Water Cooler | Nine packaged models from 62,000 to 476,000 BTU/hr | Call for rating | 9 |
| Shell & Tube Oil Coolers | Shell & Tube Oil Cooler | Seventeen sizes from a 3 inch shell 14 inches long to an 8 inch shell 72 inches long | Call for rating | 17 |
The WAC Series rejects the loop's heat to ambient air through a copper-tube, aluminum-fin radiator, and delivers the whole system as a package: pump sized to the coil and the run, a starter, an expansion tank and a three-way valve that bypasses the coil to hold the supply temperature steady as the ambient changes. Nine sizes cover 62,000 to 476,000 BTU/hr at a 90°F ambient with water from 140°F to 115°F; larger builds to 3,000,000 BTU/hr are made to order.
Because the closed loop is only as cold as the ambient air plus the approach, the WAC is usually chosen where the process is happy with 100 to 120°F water. Where colder water is needed on the hottest days, a WAC can pre-cool ahead of a small chiller and carry the full load for the rest of the year.
Nine packaged models from 62,000 to 476,000 BTU/hr.
+ Learn More
Seventeen sizes from a 3 inch shell 14 inches long to an 8 inch shell 72 inches long.
+ Learn MoreTo ambient air temperature plus the approach, so with a 90°F design ambient the standard ratings deliver 115°F water. Where the process needs colder water on the hottest days, a WAC pre-cools ahead of a small chiller and carries the whole load the rest of the year.
Only where the unit or the piping is exposed to freezing. Glycol costs capacity - allow for it in the sizing - so use the lowest percentage that protects the site.
The finned copper-aluminum coil, the fans, the circulating pump and starter, an expansion tank and a three-way control valve that bypasses the coil to hold the supply temperature steady as the ambient changes.